Analysis of sympathetic inrush phenomena in transformers using coupled field-circuit approach

DSpace at IIT Bombay

View Archive Info
 
 
Field Value
 
Title Analysis of sympathetic inrush phenomena in transformers using coupled field-circuit approach
 
Creator KUMBHAR, GB
KULKARNI, SV
 
Subject electric power systems
parameter estimation
finite element analysis
power transformers
 
Description Sympathetic inrush current phenomenon occurs when a transformer is switched on in a power system network containing other transformers which are already energized. In this paper, the phenomenon of sympathetic inrush current is investigated using nonlinear-transient field-circuit coupled finite element formulation. The cases of the transformers connected in parallel and in series have been considered. The results obtained for a 31.5 MVA, three-phase transformer are presented and discussed in detail. This work also includes the investigation of parameters affecting the magnitude and duration of sympathetic inrush phenomenon, such as series resistance, switching-on angle, residual flux density and load conditions. These analyses provide a sound theoretical basis for a thorough understanding of the phenomenon.
 
Publisher IEEE
 
Date 2008-12-10T12:54:26Z
2011-11-27T12:28:43Z
2011-12-15T09:56:33Z
2008-12-10T12:54:26Z
2011-11-27T12:28:43Z
2011-12-15T09:56:33Z
2007
 
Type Article
 
Identifier Proceeding of the IEEE Power Engineering Society General Meeting, Tampa, USA, 24-28 June 2007, 1-6
1-4244-1298-6
10.1109/PES.2007.386128
http://hdl.handle.net/10054/285
http://dspace.library.iitb.ac.in/xmlui/handle/10054/285
 
Language en