Current Differential Protection of Transmission Line Using the Moving Window Averaging Technique
DSpace at IIT Bombay
View Archive InfoField | Value | |
Title |
Current Differential Protection of Transmission Line Using the Moving Window Averaging Technique
|
|
Creator |
DAMBHARE, S
SOMAN, SA CHANDORKAR, MC |
|
Subject |
relay
system current differential protection global positioning system (gps) moving window averaging technique series-compensated lines transmission line |
|
Description |
We propose a new approach to current differential protection of transmission lines. In this approach, we transform the instantaneous line current(s) by using a moving window averaging technique. If the time span of moving window is equal to one-cycle time, then the steady-state value of the transformed current is zero for a periodic signal which is composed of fundamental and harmonic frequencies. Signal distortions ( e. g., a fault) cause the transformed currents to deviate from the nominal zero value. This permits the development of a sensitive, secure, fast, and yet simple current differential protection scheme. The scheme can be applied in toto to series-compensated transmission lines. Results on a four-machine ten-bus system and comparative evaluation with state-of-the-art methods brings out promise of the proposed method.
|
|
Publisher |
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
|
|
Date |
2011-07-31T23:27:42Z
2011-12-26T12:53:11Z 2011-12-27T05:40:23Z 2011-07-31T23:27:42Z 2011-12-26T12:53:11Z 2011-12-27T05:40:23Z 2010 |
|
Type |
Article
|
|
Identifier |
IEEE TRANSACTIONS ON POWER DELIVERY, 25(2), 610-620
0885-8977 http://dx.doi.org/10.1109/TPWRD.2009.2032324 http://dspace.library.iitb.ac.in/xmlui/handle/10054/8273 http://hdl.handle.net/10054/8273 |
|
Language |
en
|
|