Record Details

Voltage and frequency control of parallel operated synchronous generator and induction generator with STATCOM in micro hydro scheme

DSpace at IIT Bombay

View Archive Info
 
 
Field Value
 
Title Voltage and frequency control of parallel operated synchronous generator and induction generator with STATCOM in micro hydro scheme
 
Creator TAMRAKAR, I
SHILPAKAR, LB
FERNANDES, BG
NILSEN, R
 
Subject load
 
Description Parallel operation of synchronous and induction generators in micro hydro scheme is presented. The synchronous generator has an exciter, which provides a fixed excitation to produce normal rated terminal voltage at full resistive load. On the other hand, the induction generator has neither exciter nor speed controller. Static compensator (STATCOM) is connected to the common bus for terminal voltage and frequency control. A resistive dump load is connected across the DC link capacitor of STATCOM through a chopper to control active power. Simulink model is developed to perform transient analysis of the proposed scheme. Experimental results are presented to compare with the simulation results. It is found that connection of an induction generator in parallel with the synchronous is much simpler than connecting two synchronous generators in parallel.
 
Publisher INST ENGINEERING TECHNOLOGY-IET
 
Date 2011-08-03T08:25:12Z
2011-12-26T12:54:07Z
2011-12-27T05:41:32Z
2011-08-03T08:25:12Z
2011-12-26T12:54:07Z
2011-12-27T05:41:32Z
2007
 
Type Article
 
Identifier IET GENERATION TRANSMISSION & DISTRIBUTION, 1(5), 743-750
1751-8687
http://dx.doi.org/10.1049/iet-gtd:20060385
http://dspace.library.iitb.ac.in/xmlui/handle/10054/8959
http://hdl.handle.net/10054/8959
 
Language en